1.Control mode and features::
Balanced temperature system is controlled by PID and Fuzzy.
The system is stable, power saving and suitable for long time running.
2.Control mode :
a. Compared to the conventional climatic chambers, the new MHE series saves about 30~ 70% power and about 80% water consumption.
b. Running noise is about 65 dB±3dB, measured one meter away in front of chamber
3.Programmable controller Terchy S3503:
3.5inch touch screen and human machine interface
Language options: Chinese / English
Trouble diagnosis, solution and history records
User-friendly program editing functions, including edit, delete, insert, etc
Memory at power outrage
Max 8G USB interface to store and copy the test data
(Optional) Remote monitor software to link the pc with computer to monitor the running and turn ON/OFF the chamber
(Optional) Curve view software to transfer the graph to data that can open by EXCEL and print on computer
Applications
Programmable temperature & humidity chamber is used to test and determine the heat/cold resistant features and performances of electrical & electronic products and materials in specific temperatures. It is the necessary test equipment in aviation, automobile, household appliances, scientific research, etc.
Standard complied
GB/T 2423.1-2008 ( IEC 60068-2-1:2007)test A: Cold
GB/T 2423.2-2008 ( IEC 60068-2-2:2007)test B: Dry heat
GB/T 2423.3-2006 ( IEC 60068-2-78:2001)test Cab: Damp heat, steady state
GB/T 2423.4-2008 ( IEC 60068-2-30:2005)test Db: Damp heat, cyclic
MODEL |
MHE-Z |
VOLUME/CODE |
120A |
408A |
1000A |
TEMPERATURE RANGE |
-40℃~+150℃ |
HUMIDITY RANGE |
30%~95%RH |
TEMPERATURE UNIFORMITY |
±2℃
Sensor location to wall distance is 1/10 of chamber interior dimensions.(≧50mm) |
HUMIDITY UNIFORMITY |
±3%RH(actual humidity>50%RH) ±5%RH(actual humidity≤50%RH) |
TEMPERATURE CONSTANCY |
±0.3℃ |
HUMIDITY CONSTANCY |
±2.5%RH |
HEATING TIME
(WHEN EMPTY IN WORK SPACE)
|
from -40℃ to +150℃ about 60min |
COOLING TIME
(WHEN EMPTY IN WORK SPACE)
|
from +20℃ to -40℃ |
about 40min |
about 55min |
about 75min |
INTERIOR DIMENSIONS
(WxHxD)CM |
50x60x40 |
60x85x80 |
100x100x100 |
EXTERIOR DIMENSIONS
(WxHxD)CM |
70x177x120.8 |
80x180x164 |
120x195x184 |
CONTROLLER |
Terchy S3503 color 3.5 inch LCD touch screen controller |
NET WEIGHT |
308KG |
416KG |
705KG |
POWER |
AC 3ф4W+G 380V±10% 50HZ |
NOTES:
(1)Air cooling type system and water cooling system available, all performance parameters of standard air cooling chamber are measured at +20℃ ambient & when empty in workspace; all water cooling parameters are with +25℃ cooling water & when empty in workspace.
(2)Sensor measurement method comply with IEC 60068-3-6:2001/ GB/T 2424.6-2006 / JTM K09 :2009. Parameters measured when sensor location to wall distance is 1/10 of chamber interior dimensions.
(3)Pics and spec for reference only. For more details please contact your sales rep.
|
MODEL |
MHE-Z |
VOLUME/CODE |
120N |
408N |
1000N |
TEMPERATURE RANGE |
-70℃~+150℃ |
HUMIDITY RANGE |
30%~95%RH |
TEMPERATURE UNIFORMITY |
±2℃
Sensor location to wall distance is 1/10 of chamber interior dimensions.(≧50mm)
|
HUMIDITY UNIFORMITY |
±3%RH(actual humidity>50%RH) ±5%RH(actual humidity≤50%RH) |
TEMPERATURE CONSTANCY |
±0.3℃ |
HUMIDITY CONSTANCY |
±2.5%RH |
HEATING TIME
(WHEN EMPTY IN WORK SPACE)
|
from -70℃ to +150℃ about 65min |
COOLING TIME
(WHEN EMPTY IN WORK SPACE)
|
from +20℃ to -70℃ |
about 90min |
about 75min |
about 90min |
INTERIOR DIMENSIONS
(WxHxD)CM
|
50x60x40 |
60x85x80 |
100x100x100 |
EXTERIOR DIMENSIONS
(WxHxD)CM
|
70x177x120.8 |
80x180x164 |
120x195x184 |
CONTROLLER |
Terchy S3503 color 3.5 inch LCD touch screen controller |
NET WEIGHT |
322KG |
489KG |
809KG |
POWER |
AC 3ф4W+G 380V±10% 50HZ |
NOTES:
(1)Air cooling type system and water cooling system available, all performance parameters of standard air cooling chamber are measured at +20℃ ambient & when empty in workspace; all water cooling parameters are with +25℃ cooling water & when empty in workspace.
(2)Sensor measurement method comply with IEC 60068-3-6:2001/ GB/T 2424.6-2006 / JTM K09 :2009. Parameters measured when sensor location to wall distance is 1/10 of chamber interior dimensions.
(3)Pics and spec for reference only. For more details please contact your sales rep.
|